ElectroDesigner — Engineering Software
SHORT-CIRCUIT DESIGN

Transformer Short-Circuit Current Calculator

Estimate three-phase fault current at LV transformer terminals from transformer rating and impedance, with an optional upstream source fault level.

INPUTS

Transformer and source parameters

Use nameplate transformer data. Add the upstream short-circuit power when it is known; enter 0 to retain the strong-source assumption.

kVA
V
%
MVA
0 = infinite / strong source. If known, enter the three-phase short-circuit power at the transformer supply point.

This remains a symmetrical RMS estimate. It does not include transformer impedance tolerance, voltage factor, X/R-dependent peak current, downstream conductors or motor contribution.

Use 0 MVA only when the traditional infinite-source terminal estimate is what you intend to calculate.

Result

READY
TERMINAL FAULT CURRENT— kA
Transformer rated current—
Fault level at LV terminals—
Total equivalent impedance—
Source assumption—
Use the result for preliminary fault-level estimate. Protective-device interrupting rating, peak current, let-through energy and equipment SCCR/withstand require the relevant system and device data.
Verification required: Results are calculation aids and are not guaranteed to be error-free or suitable for a specific project. Independently verify inputs, outputs, applicable standards, manufacturer data and project requirements before design release, procurement or installation.

Method

The transformer impedance and optional upstream source impedance are combined on the transformer MVA base.

In = S / (√3 · U)
zsource,pu = Stransformer / Ssc,source
Isc = In / (ztransformer,pu + zsource,pu)
01 · TRANSFORMERUse actual kVA, LV voltage and nameplate uk%.
02 · SOURCEEnter upstream short-circuit power when available instead of assuming an infinite source.
03 · NEXT CHECKContinue into protection-chain analysis →

Calculation method

With an infinite source the familiar terminal estimate is Isc ≈ In × 100 / uk%. When upstream short-circuit power is entered, its per-unit source impedance is added to the transformer impedance before current is calculated.

Infinite source: Isc ≈ In / (uk% / 100)
Finite source: Isc = In / [(uk% / 100) + (Stransformer / Ssc,source)]

Worked example

Load the worked example for 1000 kVA, 400 V and uk = 6% with the upstream source left at 0 MVA. Rated current is 1443.4 A and the traditional strong-source terminal fault estimate is 24.06 kA.

Method guide: Transformer Short-Circuit Current: Worked Example shows the same calculation and the effect of finite source strength step by step.

Effect of a finite upstream source

If the same transformer is supplied from a system with 250 MVA short-circuit power, total per-unit impedance becomes 0.064 and the terminal current falls to about 22.55 kA. This illustrates why the infinite-source calculation can overstate the actual available current.

Frequently asked questions

Is this a complete IEC 60909 study?

No. It is a simplified transformer-terminal model. IEC 60909 studies can require voltage factors, network impedances, rotating-machine contribution and peak-current treatment.

What should I enter for upstream fault level?

Use the three-phase short-circuit power at the transformer supply point from the utility/network study. If it is unknown, 0 retains the explicit strong-source assumption rather than inventing a value.

Continue the design check

All calculators · FaultChain · Short-circuit and SCCR guide · Standards library

Technical reference: transformer terminal short-circuit guidance.

Engineering decisions need traceable calculations.

Use the free calculators for fast checks, or move to FaultChain Pro when the protection chain, let-through energy and equipment withstand need to be reviewed together.