Transformer Short-Circuit Current: Worked Example

Protection guide · Reviewed 22 Sep 2026 · ElectroDesigner

Transformer percentage impedance gives a fast first estimate of the available symmetrical RMS fault current at the LV terminals. The familiar infinite-source calculation is useful for screening, but a finite upstream source reduces the result and downstream cable or busbar impedance reduces it further.

1. Transformer-terminal equations

Transformer rated current on the LV side:

In = S × 1000 / (√3 × ULL)

With an infinite/strong upstream source:

Isc ≈ In × 100 / uk%

If the three-phase upstream short-circuit power is known, a simple per-unit source impedance can be added:

zsource,pu = Stransformer / Ssc,source
Isc = In / (ztransformer,pu + zsource,pu)

2. Worked example: 1000 kVA, 400 V, uk = 6%

In = 1000 × 1000 / (√3 × 400) = 1443.38 A
Isc = 1443.38 / 0.06 = 24.06 kA

The strong-source terminal estimate is therefore approximately 24.06 kA symmetrical RMS.

Run the Transformer Short-Circuit Calculator

3. What if the upstream network is only 250 MVA?

On a 1 MVA transformer base:

zsource,pu = 1 / 250 = 0.004
ztotal,pu = 0.060 + 0.004 = 0.064
Isc = 1443.38 / 0.064 = 22.55 kA

The finite source lowers the preliminary terminal current from 24.06 kA to about 22.55 kA. The exact study may need source R/X, transformer tolerances, voltage factors and other contributions.

4. Fault current away from the transformer

For a downstream fault, use the total upstream impedance at the fault location:

Isc = U / (√3 × |ZT|)
|ZT| = √(RT² + XT²)

Cable, busbar and source impedance therefore matter. The transformer-terminal value should not simply be copied to every downstream panel.

5. Assumptions and limits

Adjacent checks

Read Short-Circuit Current vs SCCR vs Interrupting Rating, then use FaultChain to carry the prospective current through a radial protection path. For selectivity, continue with Protection Coordination and TCC Explained.

Engineering references

Schneider Electric Electrical Installation Guide — transformer terminal short-circuit current and 3-phase short-circuit current at any point in an LV installation.