IEC Cable Sizing Calculator
Size a conductor against current-carrying capacity, installation method, derating, voltage drop and short-circuit thermal withstand in one traceable workflow.
Electrical load
Define the circuit operating point.
Cable & installation
Reference current rating follows the selected IEC installation method.
IEC 60364-5-52 reference method C.
Automatic mode uses IEC 60364-5-52 Annex B reference current ratings. Air temperature correction uses Table B.52.14; buried methods D1/D2 use ground-temperature Table B.52.15.
Short-circuit thermal check
Select one calculation basis. Fields not used by the selected method are disabled.
I²t mode: the entered value must be the protective device's total-clearing let-through energy for the applicable prospective fault level. Breaking capacity (Icn/Icu/Ics) is not an I²t value.
Method
The ampacity engine uses the reference installation methods and current-carrying-capacity tables of IEC 60364-5-52:2009+A1:2024. Short-circuit thermal verification follows the adiabatic concept used in IEC 60364-4-43.
Normative references: IEC 60364-5-52, Annex B · IEC 60364-4-43 · DIN VDE 0298-4 (VDE 0298-4):2023-06.
Prefer a guided verification?
Open the IEC Cable Design & Verification Workflow to work through one cable step by step from load and installation method to ampacity, protection, voltage drop, short-circuit thermal withstand and optional lifecycle economic screening. The workflow is currently PILOT.
Cable design guides and related calculators
Use the complete Cable Design cluster beside this calculator: cable sizing vs ampacity → IEC installation methods → temperature and grouping derating → three-phase voltage drop → short-circuit thermal withstand. For protection-side I²t context, see I²t let-through energy. For a North American project, use the separate NEC cable sizing calculator. To examine the upstream protection path, open the FaultChain short-circuit protection calculator.