ElectroDesigner — Engineering Software
Cable derating

Cable Derating: Ambient Temperature, Grouping and Installation Factors

Cable design guide · Reviewed 22 Sep 2026 · ElectroDesigner

Reference ampacity assumes defined reference conditions. Real projects rarely match every one of them. Higher ambient temperature, grouped circuits, thermal insulation, soil conditions and other installation effects reduce the heat a cable can continuously dissipate. Derating converts the reference current-carrying capacity into a value that represents those actual conditions.

1. The derating equation

Iz,corrected = Iz,ref × Ca × Cg × Ci × Cx …

Where the symbols are project-defined labels for the factors required by the selected standard/data source. A convenient inverse form is:

Iz,ref,required = Irequired / (Ca × Cg × Ci × Cx …)

For a protected circuit, Irequired may be driven by the protective-device rating rather than only the design current because the coordination requirement can be Ib ≤ In ≤ Iz.

2. What the main factors represent

For the IEC 60364-5-52 reference system, public engineering guidance notes 30 °C as the reference ambient air temperature for many air ratings and 20 °C as the reference ground temperature for buried ratings; the adopted table and cable construction still need to be verified for the actual project.

3. Worked example: a 57 A reference rating becomes 41.5 A

Assume verified project data give:

Iz = 57 × 0.91 × 0.80 = 41.50 A

A cable that appears to have 17 A headroom above a 40 A circuit at reference conditions now has only 1.5 A of corrected headroom. If the required protective-device rating were 50 A, the cable would fail the coordination check despite the original 57 A reference value.

The reference ampacity required for a 50 A target under the same factors would be:

Iz,ref,required = 50 / (0.91 × 0.80) = 68.68 A

This is why derating should be part of conductor selection, not a final note added after the size has already been fixed.

Open Cable Ampacity Calculator

4. Common derating mistakes

5. Assumptions and limits

The simple product-of-factors model is useful only when the source data permit those factors to be combined in that way. Some configurations require dedicated tables, manufacturer calculations, or thermal models rather than independent multipliers. For non-standard buried installations, IEC 60287 methods may be appropriate.

Do not copy a correction factor from an online example into a project without confirming cable insulation, conductor material, installation method, number of loaded conductors, spacing and the adopted standard edition.

Adjacent checks

Use the IEC installation-method guide before choosing Iz,ref. Then run the complete IEC Cable Sizing Calculator so ampacity, voltage drop and short-circuit thermal withstand are reviewed together.

Engineering references

IEC 60364-5-52:2009+AMD1:2024 is the current consolidated wiring-systems reference. Public examples of temperature, soil and grouping corrections are described in the Electrical Installation Guide — General method for cable sizing.

Keep the cable checks connected.

A cable size is only complete when ampacity, installation conditions, voltage drop, protection and short-circuit thermal withstand have all been checked on the same design basis.