Cable Derating: Ambient Temperature, Grouping and Installation Factors
Reference ampacity assumes defined reference conditions. Real projects rarely match every one of them. Higher ambient temperature, grouped circuits, thermal insulation, soil conditions and other installation effects reduce the heat a cable can continuously dissipate. Derating converts the reference current-carrying capacity into a value that represents those actual conditions.
1. The derating equation
Where the symbols are project-defined labels for the factors required by the selected standard/data source. A convenient inverse form is:
For a protected circuit, Irequired may be driven by the protective-device rating rather than only the design current because the coordination requirement can be Ib ≤ In ≤ Iz.
2. What the main factors represent
- Ambient temperature: cable ratings are based on a reference ambient condition. A hotter environment generally reduces permissible current.
- Grouping: adjacent loaded circuits heat one another and reduce heat dissipation.
- Installation condition: thermal insulation, ducts, buried routes and enclosure conditions can change the rating basis or introduce additional factors.
- Soil conditions: buried cables can require corrections for ground temperature and soil thermal resistivity.
- Other effects: harmonics, loaded neutrals, cyclic loading or manufacturer-specific installation limits may require separate treatment.
For the IEC 60364-5-52 reference system, public engineering guidance notes 30 °C as the reference ambient air temperature for many air ratings and 20 °C as the reference ground temperature for buried ratings; the adopted table and cable construction still need to be verified for the actual project.
3. Worked example: a 57 A reference rating becomes 41.5 A
Assume verified project data give:
- Iz,ref = 57 A;
- ambient-temperature factor Ca = 0.91;
- grouping factor Cg = 0.80;
- all other factors = 1.00.
A cable that appears to have 17 A headroom above a 40 A circuit at reference conditions now has only 1.5 A of corrected headroom. If the required protective-device rating were 50 A, the cable would fail the coordination check despite the original 57 A reference value.
The reference ampacity required for a 50 A target under the same factors would be:
This is why derating should be part of conductor selection, not a final note added after the size has already been fixed.
Open Cable Ampacity Calculator
4. Common derating mistakes
- Double counting: applying a factor already embedded in the chosen reference rating.
- Mixing bases: taking Iz,ref from one installation method and correction factors from another.
- Using one factor for the whole route: ignoring a short but thermally severe section through insulation or a congested tray.
- Ignoring loaded neutrals/harmonics: especially where triplen harmonic content materially loads the neutral.
- Treating a design margin as a standards factor: a project margin is useful but must remain distinct from normative correction factors.
5. Assumptions and limits
The simple product-of-factors model is useful only when the source data permit those factors to be combined in that way. Some configurations require dedicated tables, manufacturer calculations, or thermal models rather than independent multipliers. For non-standard buried installations, IEC 60287 methods may be appropriate.
Adjacent checks
Use the IEC installation-method guide before choosing Iz,ref. Then run the complete IEC Cable Sizing Calculator so ampacity, voltage drop and short-circuit thermal withstand are reviewed together.
Engineering references
IEC 60364-5-52:2009+AMD1:2024 is the current consolidated wiring-systems reference. Public examples of temperature, soil and grouping corrections are described in the Electrical Installation Guide — General method for cable sizing.