ElectroDesigner — Engineering Software
Cable short-circuit withstand

Cable Short-Circuit Thermal Withstand: I²t ≤ k²S²

Cable design guide · Reviewed 22 Sep 2026 · ElectroDesigner

A cable can carry its normal load current and still be thermally damaged by a short circuit before the protective device clears. The short-circuit thermal check compares the fault energy passed through the conductor with the thermal energy the conductor and insulation can withstand for the applicable temperature limits.

1. The adiabatic short-circuit relationship

I²t ≤ k²S²

Equivalent useful forms are:

Smin = I × √t / k
tmax = (kS / I)²

Where:

The relationship is an adiabatic approximation: during the short event, heat loss from the conductor is neglected. Public IEC-based design guidance applies this form for short durations up to about 5 s, subject to the standard's conditions.

2. Worked example: 10 kA cleared in 0.20 s

Assume:

Smin = 10,000 × √0.20 / 143 = 31.27 mm²

The next standard conductor size would therefore be 35 mm² if no larger criterion governs.

Check the selected 35 mm² conductor directly:

Fault I²t = 10,000² × 0.20 = 20,000,000 A²s
Cable k²S² = 143² × 35² = 25,050,025 A²s

Under those assumptions, the 35 mm² conductor passes the adiabatic thermal check.

For comparison, using k = 115 for a copper/PVC example basis would give:

Smin = 10,000 × √0.20 / 115 = 38.89 mm²

That would move the thermal minimum to the next suitable standard section. The k value is therefore not a generic material constant; its temperature/insulation basis matters.

3. Current-limiting fuses and breakers: use the right I²t

If a protective device is strongly current limiting, the simple prospective-current × clearing-time rectangle can be overly conservative or physically unrepresentative. Where the applicable engineering method permits, compare the conductor limit with the device manufacturer's verified total-clearing let-through I²t for the relevant prospective fault level:

I²tdevice,total-clearing ≤ k²S²

Do not use breaking capacity (Icn, Icu, Ics or a fuse interrupting rating) as if it were an I²t value. Interrupting capability and let-through energy are different characteristics.

Check short-circuit thermal withstand in IEC Cable Sizing

4. Limits of the adiabatic model

5. Practical design workflow

  1. Calculate maximum and minimum fault-current conditions at the cable location.
  2. Confirm protective-device breaking capacity separately.
  3. Obtain the clearing time or verified total-clearing I²t at the relevant prospective fault level.
  4. Select k from the adopted standard/data source for the conductor/insulation temperature basis.
  5. Check I²t ≤ k²S².
  6. Verify that the same cable also passes continuous ampacity and voltage-drop criteria.
  7. For current-limiting coordination, retain the manufacturer curve/table reference used for I²t.

Adjacent checks

Read I²t Let-Through Energy Explained for the protection-side concept, then use FaultChain when you need to review upstream fault current and protection as a chain rather than as an isolated cable calculation.

Engineering references

IEC 60364-4-43:2023 is the current IEC overcurrent-protection publication. IEC 60949 covers thermally permissible short-circuit currents including non-adiabatic heating effects. A public IEC-based worked-method reference is the Electrical Installation Guide — cable short-circuit withstand.

Keep the cable checks connected.

A cable size is only complete when ampacity, installation conditions, voltage drop, protection and short-circuit thermal withstand have all been checked on the same design basis.