Motor FLC Calculator
Estimate motor full-load current from output power, system voltage, efficiency and power factor.
Calculation parameters
Enter project values below. The result updates when you calculate.
Result
READYMethod
Mechanical output power is converted to electrical input power using efficiency, then current is obtained from real power and power factor.
3φ: I = Pout / (√3 · V · η · cosφ)
Calculation method
Worked example
Load the worked example: 7.5 kW, 400 V three-phase, η = 0.90 and PF = 0.85. Estimated FLC is about 14.15 A; a 1.25 design multiplier gives 17.69 A and a 6× starting-current estimate gives about 84.9 A.
Frequently asked questions
Can I use this value as the breaker setting?
No. Check nameplate current, starting behaviour, the applicable code and manufacturer coordination data.
Which standards should I use?
Use the edition adopted for your project and jurisdiction. See the standards library for the scope of IEC, UL and NEC references.