Earthing & Grounding Checks
Select one method. A PE thermal check, a TT protective-measure criterion and an analytical rod estimate answer different questions and must not be treated as one compliance result.
Method boundaries and sources
The page separates three calculations because they have different inputs and evidence:
PE · IEC 60364-5-54: S = I√t/k. The next listed conductor size is only a catalogue aid; check mechanical minima and the complete protective-conductor design. Official standard IEC 60364-5-54.
TT · IEC 60364-4-41: RA,max = UL/IΔn, using measured installation RA. The result assesses this inequality only. Verify the selected UL under the applicable national and special-location rules. Official standard IEC 60364-4-41.
Rod estimate · R ≈ ρ/(2πL)[ln(4L/d) − 1]. This is an analytical approximation, not a normative pass/fail test. Confirm by field measurement under IEC 60364-6 with suitable equipment. Verification standard IEC 60364-6.
Standard and scope
Excluded from all three results: lightning protection, high-voltage earthing, soil stratification, multiple electrodes, RCD timing and selectivity, and complete automatic-disconnection verification.