Power Factor Correction Worked Example: kVAr, kVA and Current
Power-factor correction reduces reactive power and apparent power for the same active kW. For a sinusoidal load model, the required capacitor-bank rating follows directly from the change in phase angle between the existing and target power factors.
1. Core equations
Apparent power before and after correction is:
For a balanced three-phase system:
2. Worked example: 100 kW from PF 0.78 to 0.95
Assume a 100 kW, 400 V three-phase load operating at power factor 0.78. The target is 0.95.
The theoretical requirement is therefore about 47.36 kVAr. A real installation normally uses practical capacitor-bank steps rather than treating 47.36 kVAr as an equipment catalogue rating.
3. What happens to kVA and current?
The active load remains 100 kW; the upstream apparent-power requirement and line current fall because less reactive current is supplied from the source.
Run the Power Factor Correction Calculator
4. Practical capacitor-bank selection
- Calculate the theoretical kVAr requirement at the governing operating point.
- Check the load profile so a fixed bank does not over-compensate at light load.
- Use automatic stepped compensation where the reactive demand varies materially.
- Check utility or project limits for the target power factor rather than automatically aiming at unity.
- Assess harmonic distortion and resonance before selecting a plain capacitor bank on networks with drives, UPS systems or other nonlinear loads.
- Verify voltage, frequency, switching duty, capacitor tolerance, detuning reactor and manufacturer thermal limits.
5. Assumptions and limits
- The equations above use the displacement power factor model for a sinusoidal fundamental-frequency calculation.
- Distortion power factor in harmonic-rich systems needs separate consideration.
- Capacitor banks can interact with network inductance and create or amplify resonance.
- Correction does not reduce the active kW consumed by the load.
- Final step sizes, detuning and switching arrangement must be selected for the actual network and load profile.
Adjacent checks
Use the Harmonic Filter Sizing Calculator before adding capacitors to a harmonic-rich network, and read Active vs Passive Harmonic Filters when mitigation strategy is part of the same power-quality study.
Engineering references
Method reference: Schneider Electric Electrical Installation Guide — theoretical principles to improve power factor and the wider Power Factor Correction chapter. The guide gives the same Qc = P(tanφ − tanφ′) relationship and emphasizes installation-specific compensation selection.