  "version": "2026-09-09-starter",
  "records": [
    {
      "manufacturer": "Mersen",
      "part": "AJT200",
      "type": "Fuse",
      "facts": "200 A; 600 V AC; 50/60 Hz. UL interrupting rating 200 kA RMS.",
      "coverage": "Interrupting-rating records only. No peak or I²t dataset imported.",
      "source": "https://www.mersen.com/en/products/ajt-class-j-time-delay/ajt200",
      "revision": "AJT datasheet ©2026; product page retrieved 2026-09-09",
      "page": "PF16–17; Technical Specifications"
    },
    {
      "manufacturer": "Littelfuse",
      "part": "JTD030",
      "type": "Fuse",
      "facts": "30 A; 600 V AC; 200 kA AC interrupting rating. Tabulated total-clearing I²t: 4,754 A²s at 200 kA.",
      "coverage": "Isolated published value, not a curve. Frequency/test conditions and maximum-versus-typical classification are not established here; reference only, not automatically evaluated.",
      "source": "https://www.littelfuse.com/assetdocs/jtd-datasheet?assetguid=4c6df169-2072-4ee8-a964-1d5d7d90f721",
      "revision": "2024-02-28",
      "page": "2–4"
    },
    {
      "manufacturer": "Littelfuse",
      "part": "JTD060",
      "type": "Fuse",
      "facts": "60 A; 600 V AC; 200 kA AC interrupting rating. Tabulated total-clearing I²t: 10,450 A²s at 200 kA.",
      "coverage": "Isolated published value, not a curve. Frequency/test conditions and maximum-versus-typical classification are not established here; reference only, not automatically evaluated.",
      "source": "https://www.littelfuse.com/assetdocs/jtd-datasheet?assetguid=4c6df169-2072-4ee8-a964-1d5d7d90f721",
      "revision": "2024-02-28",
      "page": "2–4"
    },
    {
      "manufacturer": "Littelfuse",
      "part": "JTD100",
      "type": "Fuse",
      "facts": "100 A; 600 V AC; 200 kA AC interrupting rating. Tabulated total-clearing I²t: 68,150 A²s at 200 kA.",
      "coverage": "Isolated published value, not a curve. Frequency/test conditions and maximum-versus-typical classification are not established here; reference only, not automatically evaluated.",
      "source": "https://www.littelfuse.com/assetdocs/jtd-datasheet?assetguid=4c6df169-2072-4ee8-a964-1d5d7d90f721",
      "revision": "2024-02-28",
      "page": "2–4"
    },
    {
      "manufacturer": "ABB",
      "part": "S204M-C32 / 2CDS274001R0324",
      "type": "MCB",
      "facts": "32 A; 4 poles; C characteristic; S200 M-C catalogue Icn 10 kA.",
      "coverage": "Reference only. Exact application conditions and curve points must be confirmed before import. Icn is not Icu or Ics.",
      "source": "https://search.abb.com/library/Download.aspx?Action=Launch&DocumentID=9AKK107991A8329&DocumentPartId=&LanguageCode=nl",
      "revision": "Document 9AKK107991A8329; retrieved 2026-09-09",
      "page": "48–49"
    },
    {
      "manufacturer": "LAPP",
      "part": "1119303 / ÖLFLEX CLASSIC 110 3G1.5",
      "type": "Cable",
      "facts": "Three conductors including PE; 1.5 mm² per conductor; copper; PVC insulation; 300/500 V.",
      "coverage": "Reference only. No k-value, short-circuit temperature limits or ampacity is assigned from this listing.",
      "source": "https://sa.lapp.com/products/olflex-classic-110-3g1-5",
      "revision": "Undated product page; retrieved 2026-09-09",
      "page": "Product make-up / Technical Data"
    }
  ]
}